Western Australian Current Regulations

[Index] [Table] [Search] [Search this Regulation] [Notes] [Noteup] [Previous] [Next] [Download] [Help]

WORK HEALTH AND SAFETY (MINES) REGULATIONS 2022 - REG 656C

656C .         Additional ventilation requirements for diesel units

                If there is at least 1 diesel unit operating underground at an underground mine, the mine operator of the mine must ensure —

            (a)         for a mine where 1 diesel unit is operating underground in any ventilation system of the mine — that the diesel unit has a ventilation volume rate of not less than 0.05 m 3 per second per kilowatt of the maximum rated engine output specified by the manufacturer, for the fuelling and timing configuration at which the engine has been set; and

            (b)         for a mine where more than 1 diesel unit is operating underground in any ventilation system of the mine — the total ventilation volume rate of air in that system is not less than the aggregate of the volume requirement for each of the individual diesel units under paragraph (a).

        Penalty:

            (a)         for an individual, a fine of $7 000;

            (b)         for a body corporate, a fine of $35 000.

        Notes for this Subdivision:

        1.         In relation to airborne contaminants and hazardous atmosphere see Part 3.2 Divisions 7, 7A and 8.

        2.         In addition to the above provisions and this Subdivision, see Subdivision 2.

        3.         See the rest of this Division in relation to underground mines.



AustLII: Copyright Policy | Disclaimers | Privacy Policy | Feedback